Jo asked ... How to engage clutch on old sewing machine to engage needle?    |    Jacky asked ... Miele Vacuum cleaner?    |    Ben asked ... Toyota Yaris French or Japanese?    |    Andy asked ... How can I mend my MacAlistair 450w hedge trimmer?    |    Felix asked ... Hitachi vt-m70em?    |    Click here to ask your question

water pump?

it seems like the pump is not pumping water round the system, i have checked and it is, the boiler takes a couple of mins to get to 70 deg then trips out?
alan, May 2009
Does pump sound like it is running, you may need to put your ear to a screwdriver handle with the tip on the front of the pump,
Have you bled all air from the system?
Is the system pressure correct?
the Impellor(fan) may have broken away from the shaft inside the pump, this will sound like the pump is running, but no circulation will occur

www.elanar.co.uk, May 2009