1 hour ago Ela asked ... Worcester 30 Cadillac combi boiler won’t fire up and the EA?    |    Alan asked ... Problem with JCB 3CX transmission?    |    Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    Click here to ask your question

over pressure on baxi 105e even though boiler is turned off?

i have a baxi 105e and even with the boiler turned off, it keeps overpressurising and lifting the safety valve. ive checked the expansion tank and the bladder pressure is 0.5 bar, which is correct according to the manual. it was suggested that it may be the hot water plate heat exchanger but i cant see how water gets into the heating circuit, could someone please enlighten me. much appreciated.
joshua maher, May 2009
CHECK THAT YOUR FILLING LOOP IS NOT LETTING WATER BY.IE MAKE SURE THAT THE LOOP IS DISCONNECTED

BRIAN, May 2009
un do your filling loop and c if it is passing water from the mains into the heating circuit if it isnt it will be deffinetly your plate heat exchanger

plumbbob, May 2009