Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

what type of terminal should i have on the flue for a worcester heatslave 2?

what type of terminal should i have on a vertical flue for a worcester heatslave 20/25 oil combi boiler, i have black smoke coming out, is it anything to do with airflow
Andy, May 2009
Is it a Balanced flue ? if so it should have the manufacturers Flue terminal kit fitted

If it is a Conventional Chimney it should be lined and have a "Chinamans Hat" type Cowl to stop rainwater.

You don't say how old the boiler is but i'm guessing that it is not new, if it has worked OK for a year or so it probably needs a good Service by an OFTEC Engineer who will be able to clean and then set the burner to give clean & efficient combustion

www.oftec.org will assist in finding a r3egistered technician near to you

www.elanar.co.uk, May 2009