Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    tom schwartz asked ... Bosch maxx 6?    |    Noman asked ... Reverse light switch?    |    Suzie asked ... Stuck Feed dog?    |    Click here to ask your question

in combi boiler, hot water become too hot and too cold?

in vokera linea 24 combi boiler, when i use shower, water become too hot or too cold, Why?
human, June 2009
when running the shower, look at led display - usually between 40ish to 50ish, when the burner goes out quickly isolate the water supply to boiler - black lever below boiler - then look at led display, if in the 90's then I would suspect a blocked domestic heat exchanger.

Big A, July 2009
the 2nd thermistor is under the outer casing on the right hand side screwed into the hot water output pipe

paul, June 2009
maybe your 2nd thermistor - i tested mine as follows
01, remover outer case ( 3 screws underneath )
02, turn off power switch
03, turn off water supply ( Black tap bottom right)
04, open hot water tap ( to drain off water )
05, remover black wire to thermistor and black sleeve ( carefully )
06, unscrew thermistor with spanner ( catch bit of water with cloth )
07, now you will need a blank plug the same size thread as the thermistor to block the hole up
08, screw the the blank plug in its place
09, connect the thermistor back on its wire
10, close the hot tap
11, turn on water supply to the boiler, check for leaks
12, switch power back on
13, test boiler by turning on the hot tap

hope this helps.

paul, June 2009
link Click here to see other fixes for Vokera.