4 hours ago Jo asked ... How to engage clutch on old sewing machine to engage needle?    |    Jacky asked ... Miele Vacuum cleaner?    |    Ben asked ... Toyota Yaris French or Japanese?    |    Andy asked ... How can I mend my MacAlistair 450w hedge trimmer?    |    Felix asked ... Hitachi vt-m70em?    |    Click here to ask your question

Baxi 105E spark generator?

When hot tap turned on boiler does not ignite for about 15 seconds then fires causing a whoomp service engineer is going to replace spark generator boiler locks out and shows flame failure go to reset and the boiler ignites any suggestions
PATRICK PIPER, August 2009
try to adjust the air amount which controlled by the servo motor and also check the gas regulator( or solllar pump)

abo ziad (egypt), June 2012
boiler now ok did not work when engineer fitted spark generator we rang baxi and they have changed wiring on it brown is now blue and blue now brown boiler came on first time cost me £120 many thank every one

patrick piper, August 2009
firstly check the spark gap, the distance between the electrode and the burner should be about the same as the width as a pound coin as a general rule of thumb. also check the gas ignition pressure, if it's too high or too low then it can cause a similar problem.

Ian, August 2009
Has he actually diagnosed the spark gen or is he guessing? I would have a) service boiler, b) checked ignition electrode and lead before coming to spark gen conclusion, however he may well be right!

www.elanar.co.uk, August 2009
link Click here to see other fixes for Baxi 105E.