4 hours ago Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    tom schwartz asked ... Bosch maxx 6?    |    Noman asked ... Reverse light switch?    |    Click here to ask your question

ariston microGENUS 23/27 MFFI not igniting?

The boiler's pump and fan come one. The electrodes spark, the clicks are audiable. After about ten seconds or so the process stops and the red light comes on. this can be repeated by pressing the reset button. Why does the boiler not burn? The gas valve gets the 230 volts supply and the 9 volts for the solinoid. Is there any other possibility than that the gas valve might be faulty? would be grateful for any suggestion,
Gee, September 2009
and/or the detection probe might be faulty or need adjusting

mert, January 2010
might be the soft start check the manual on this

mert, January 2010
sounds like the gas valve solenoid isn't lifting. new gas valve req, job for a qualified engineer.

Ian, September 2009