andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

my betacom 30 combi is operating at 3.5/4.0 bar ?

is there a way of safely bringing the pressure down to a reasonable working pressure
jamie, November 2009
put a hose on boiler drian point release pressure to 1 bar. fire boiler and whatch pressure if this starts to rise above 2.5 bar. I would suggest the expansion vessel as deflated. I would allso be thinking why as PRV NOT activated is this faulty.

kw, November 2009
Yep - bleed off water at a convenient radiator valve. Be patient - you'll need a few pints removed.

John, November 2009