GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

room thermostats?

I managed to reduce the pressure on my vaillant ecotec pro boiler following your instructions, but when I turn the heating on it justs keep rising (as does the teperature!) When I turn t off to prevent it going into the red, the latest eror measage I have is S30(no demand from rom thermosts). None of my radiators have a thermostst! any idea what i'm doing wrong?
ice maiden, November 2009
s30 is just no demand for heat from external controls ie programmer or roomstat.

boiler shouldnt run without pump spinning but that would give you rapid pressure rise if it suddenly failed 0-3 bar in a second, but like i said it shouldnt allow boiler to run so you wouldnt be able to put it on until rectified so,
other option is expansion vessel but generally from cold to rise over 3 bar would take around 5 mins.

basically as your sealed heating system full of water heats up, water expands and the expansion vessel is where expansion is allowed to take place, should this have no air charge or be full of water then there is no room for expansion and pressure will rise beyond 3 bar and pressure relief valve will open to protect boiler and let excess water out to try and lower pressure.

clear as mud?

ste, November 2009
link Click here to see other fixes for Vaillant.