Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

room thermostats?

I managed to reduce the pressure on my vaillant ecotec pro boiler following your instructions, but when I turn the heating on it justs keep rising (as does the teperature!) When I turn t off to prevent it going into the red, the latest eror measage I have is S30(no demand from rom thermosts). None of my radiators have a thermostst! any idea what i'm doing wrong?
ice maiden, November 2009
s30 is just no demand for heat from external controls ie programmer or roomstat.

boiler shouldnt run without pump spinning but that would give you rapid pressure rise if it suddenly failed 0-3 bar in a second, but like i said it shouldnt allow boiler to run so you wouldnt be able to put it on until rectified so,
other option is expansion vessel but generally from cold to rise over 3 bar would take around 5 mins.

basically as your sealed heating system full of water heats up, water expands and the expansion vessel is where expansion is allowed to take place, should this have no air charge or be full of water then there is no room for expansion and pressure will rise beyond 3 bar and pressure relief valve will open to protect boiler and let excess water out to try and lower pressure.

clear as mud?

ste, November 2009