I have one of these boilers,the code is listed as below
Code = Meaning
F 22 = DRY FIRE
Causes (thinks to be checked according to manual )
Too little water in appliance.water pressure senor defective,cable to pump or water sensor defective , pump blocked or defective , pump output to low.
All you can do is check the pressure gauge if on 0 or low refill the system via the filler loop to 1 -1.5 bars, bleed it, and then retry it.
if o k pop head out side and check the blow off valve (P,R,V) IS NOT PASSING. if it does further investigation of the boiler is needed. especially the expansion vessel
wirecutterman, December 2009