Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

heatline condensing boiler?

When the heating is on , the water pressure rises from 1.2 bar to 3.0 , the window flashes blue with code FO 3.0 i assume this means the pressure is too high , what causes the pressure to rise , the domestic hot water side of the boiler works ok.
Steve Blake, December 2009
all the lights are off on my boiler and is not working what can i do please thanks for ur help

roy, January 2010
Hi Dave,
Thanks for your help , it appears the vessel was plugged with black gunge , flexi was ok , cleaned it all out , kickspace unit fitted all working ok now.Thanks for your help and info much appreciated.

steve blake, January 2010
Thanks Dave, i will check after chrimbo , need to drain system to do it , gert does not want me to meddle with it till then , i am going to add a plinth heater to system while i am at it will let you kmow what i find , by the way it does have a flexi hose to the vessel but the rear connection is at the back of the boiler, looks a bit of an arse to get at!!!

Steve, December 2009
drain off a radiator at bleed valve and pressure should drop ,your auto fill may be open or stuck

madtyke, December 2009
hi dave here.The heatlines that have a silver flexi hose connected to the expansion vessel in the boiler are prone to blockage !! this is one possibilty. Checking vessel is also a must do.

dave., December 2009