I've had loads of problems with LF on the 130HE. For the first 3 months, it was the fact that the condensate pipe was sagging in the middle as it made its way (almost horizontally) to the outside wall of the house. This caused it to be blocked with accumulated water and the condensate trap consequently overflowed. There are two electrical contacts on the top of the condensate trap which, when bridged by water overflowing from the trap, cause shutdown and LF to be displayed. Unfortunately, if there is a slight leak of water from the heat exchanger, this can also dribble down and land on the contacts, causing the same symptoms.
Richard, March 2010