Andrew - C asked ... Stannah 400?    |    Liam asked ... Belts for old WEBB Mower?    |    Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    Click here to ask your question

my hot water is running tepid to cold?

i can't take a shower or hot bath because the water temperature on the boiler fluctuates between 20 and 52. the heating is fine.
tina allman, January 2010
I have a iIdeal combi boiler, I tap run hot and cold,no heating from some of the heaters sometimes burner comes on and off. New Boiler fitted about 2yrs

Marcia, January 2010
you dont say if your boiler is a combi or not. if it is.
1. does the boiler go on and off regularly with hot tap running? if so. plate heatexchanger getting blocked. will need replacing and system flushing out.
2. run hot tap,(with heating off) and check if radators are heating up,if so,diverter valve faulty. hope this helps

corgi 110, January 2010