narnia asked ... Matsui ct-111ss?    |    Jason asked ... How to fix handset problems ( intercom ) and access control?    |    andy asked ... Samsung VP-D60 camcorder?    |    Shopper asked ... Poor Renault Radio Reception?    |    reg bardle asked ... Lg 7kg dd?    |    Click here to ask your question

what size fuse ?

ive just fitted a second hand storage heater a unidare
WMS724N i need to know what amp fuse to use in the main fuse board
Bob couzins, January 2010
Contact www.tilmar.co.uk for storage heater repair, replace and removal services.

Martin, August 2010
There should be a Rating Plate on the heater showing the Power in kilowatts (kW)

Watts divided by Volts = Current - have the fuse a little higher else it will blow...

For instance...
2kW divided by 230 Volts = 8.7A so a 10A fuse will do

In 110V land the current will be roughly double

The fuse should not exceed the current-carrying capacity of the house cables supplying the equipment.

The combined maximum load (Current) should be safely within the range of cable.

The fuse should be sufficient to supply all the equipment on the circuit.

The main purpose of the fuse is to prevent the cables overheating and catching fire - not to protect the appliance.

Good luck...

Peccavi, January 2010