narnia asked ... Matsui ct-111ss?    |    Jason asked ... How to fix handset problems ( intercom ) and access control?    |    andy asked ... Samsung VP-D60 camcorder?    |    Shopper asked ... Poor Renault Radio Reception?    |    reg bardle asked ... Lg 7kg dd?    |    Click here to ask your question

over pressurised boiler?

how do u get boiler to work its gone to 3 on the pressure how do i take water back to 1/12
s walton, May 2010
As you read this if your boiler is a combi consider how has the pressure gone high, has it sneaked up there over time or risen there rapidly.If it is the latter then you may have issues within (a)The heating exchanger.(b) Your top-up v/vs and hose passing and letting water into your system.However to bring back to 1 to 1.5bar best to have the boiler off.Go to the nearest rad and vent off into a container water from the rad, have someone observe the gauge and stop venting at the 1bar reading. Make certain the top-up v/vs are shut, put a demand on your boiler from your domestic hot water tap check that the system pressure does not rise back up to 3 if it does then your exchanger is leaking.

Guytawe, May 2010