Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

connecting siemiens rdh10rf/set to valliant eco tec pro 24?

i have a siemens rdh10rf/set to connect to my valiant ecotec pro 24 boiler but am confused as to why it is not working need to confirm the terminals i have connected two are correct live and neutrat are correct but the l1, l2 and lx? which one should i connect and to which terminals 3,4 or 5?

help
KROBERTSANDSONS, September 2010
Permernant L & N from boiler to L & N on stat.
Boiler terminal 3 to lx on stat.
l1 on stat to terminal 4 on boiler.

Carefree, September 2010