Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

worcester heatslave?

my worcester heatslave 18/25 system-one of the radiators we frequently have to bleed, as it goes cold,and then the pressure drops, and we have to top that up .is this usual
Lynda williams, September 2010
Expansion vessel has a torn diaphragm. I replace 60-70 of these a year. It needs to be replaced and the system volume needs to be calculated to make sure there is enough expansion volume (manufacturer states this). If it was me, I'd get an engineer to put a half inch cap on the heat exchanger tapping and fit you an 18L vessel minimum before any valve on the central heating system (close to boiler). Reason being is the Worcester vessel is dear (part number 87161425050) but an 18L standard vessel is about one third the price and will last longer. I have just fitted an 18/25 heatslave for a friend with a total of 30L expansion. I'd do this job for £100 locally so don't pay much more.

Oil Only, October 2010