Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

worcester bosch heatslave 20/25 pressure high and overflow active?

when hw and or ch is selected pressure rises past 3 bar and the overflow is active.
when turned off pressure reduces slightly but overflow still active.
all rads fully functional and hot.
smudge 5815, October 2010
Possibly overfilled, make sure the filling loop is turned off.
If the pressure rises significantlyon using HW/CH, it could be the expansion vessel needs re-charging/replacing.
If the 'overflow' continues to leak the prv has failed and will need replacing.

Carefree, October 2010