Ben asked ... Toyota Yaris French or Japanese?    |    Andy asked ... How can I mend my MacAlistair 450w hedge trimmer?    |    Felix asked ... Hitachi vt-m70em?    |    Katie Bond asked ... Fixing auto threader on Baby Lock Enlighten Overlocker?    |    Chris. asked ... Miele W800 novotronic washing machine?    |    Click here to ask your question

worcester bosch heatslave 20/25 pressure high and overflow active?

when hw and or ch is selected pressure rises past 3 bar and the overflow is active.
when turned off pressure reduces slightly but overflow still active.
all rads fully functional and hot.
smudge 5815, October 2010
Possibly overfilled, make sure the filling loop is turned off.
If the pressure rises significantlyon using HW/CH, it could be the expansion vessel needs re-charging/replacing.
If the 'overflow' continues to leak the prv has failed and will need replacing.

Carefree, October 2010