GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

Betacom 24c boiler pressure too high?

Boiler pressure is indicating 3 Bar. I have taken out about 2+ gallons of water from a drain valve on the nearest radiator. But the pressure drops but then returns to around 3 Bar within less than a minute, after closing the drain valve each time.
Should the cold water inlet tap below the boiler be open or closed for normal operation and during the water drain?
DC, October 2010
inlet valve ie, filling loop should be closed

RJ, October 2010