Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    tom schwartz asked ... Bosch maxx 6?    |    Noman asked ... Reverse light switch?    |    Suzie asked ... Stuck Feed dog?    |    Click here to ask your question

Pressure High on boiler?

I have a Vokera Combi 24 boiler, installed about three years ago. recently pressure has risen from 1.5 bar (normal) to 3 bar at which it then leaks slightly. have been told expansion vessel need replacing/fixed but also conflicting infomation stating that I need the system flushed as it is choked and this is why the pressure keeps going up.

Can you please help?
Yvonne, November 2010
Hi there, I am no expert BUT??? I have just had the same problem myself and sorted it out myself at very little cost.

First you have release the pressure by either useing your PRESSURE SAFETY VALVE it is red in colour with a black pull tab (number 27) in your instruction book (page 55). this will release the pressure which the water will then go outside via your overflow pipe.or, draning water from your radiator

Close your valve that fills the loop the one that you have to use to build your pressure up (number 7 in your instructions) make sure it is in the horizontal position. remove one end of the loop ( No 8 flexible hose ) make sure that you have a container to catch any excess water.

Turn your valve back to the upright position, NOW !! if you have any water coming from your loop then your problem is your STOP/FILL VALVE (No 7) which is allowing small amounts of water though which could be the problem of your pressure build up.

makzy, November 2010