GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

drayton digistat 30002/RF601?

thermostat calling for heating no response from ideal he24 boiler
paul, November 2010
if boiler is an isar reciever will be somewhere near boiler, if it is an icos could be near boiler or in airing cupboard. will say on front digistat scr. 2 light options on front of reciever, green or red. for heating to come on you need a green light. if reciever is showing a red light it is not getting a signal from room stat, either need to replace batteries in room stat or room stat faulty. if you have a green light on reciever and boiler not firing for heating, the boiler may show a 0 on display, no signal for heating to work, or a c with the burner light flashing, possible divertor valve. if green light on and 0 on display, programmer must also be on to make ch work, need to check reciever. to do this turn room stat down to minimum and green light should go off. next turn digistat up to max and as green light comes on you should hear a click from reciever box. if this doesnt happen you have a faulty reciever box . to check, may need 2 people depending on location of room stat and reciever

gary, November 2010