GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

I Have a Britony combi SE boiler I have had to remove and refit a radiator ?

I Have a Britony combi SE Boiler and have removed a refitted a radiator i have opend all the valves on the rads to release any air but the boiler is still showing fault 40 and 80 low water pressure in central heating circuit.Can anyone please help.
Phil, November 2010
your boiler needs to be topped up via filling loop.usually a braided hose attatched tot two valves under the boiler on pipework.the valves are closed when the slot or handle are accross the pipes.open the valves inline one at a time allow the presure in slowly until your gauge reads just above one bar.

deano, November 2010