Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

I Have a Britony combi SE boiler I have had to remove and refit a radiator ?

I Have a Britony combi SE Boiler and have removed a refitted a radiator i have opend all the valves on the rads to release any air but the boiler is still showing fault 40 and 80 low water pressure in central heating circuit.Can anyone please help.
Phil, November 2010
your boiler needs to be topped up via filling loop.usually a braided hose attatched tot two valves under the boiler on pipework.the valves are closed when the slot or handle are accross the pipes.open the valves inline one at a time allow the presure in slowly until your gauge reads just above one bar.

deano, November 2010