narnia asked ... Matsui ct-111ss?    |    Jason asked ... How to fix handset problems ( intercom ) and access control?    |    andy asked ... Samsung VP-D60 camcorder?    |    Shopper asked ... Poor Renault Radio Reception?    |    reg bardle asked ... Lg 7kg dd?    |    Click here to ask your question

vokera linea 24 boiler?

bar pressure gauge keeps dropping to 0 ,fill up to about 2,heating and hot water ok but will gradually lose pressure and dropp to nil? help or advice grateful
pete, December 2010
had this on same boiler.mine turned out to be safety valve leaking. cost 20 pounds, real easy fix to replace. also i topped up the expansion vessel with foot pump, works a treat

dave, January 2011
1: Leak on system
2: Leaking prv
3: Expansion vessel needs recharging/replacing

Carefree, December 2010
link Click here to see other fixes for Vokera.