Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

How can I fix my potterton floor standing boiler?

I have a potterton kingfisher floor standing boiler,which carries about 18 rads the rads on the top floor will not get hot. I have tried turning off the rads at the bottom , and leaving the top ones on, I have bleed them for three day. I have check the tanks, the top rads only get hot at the bottom of the rads.
Derek, January 2011
I'll assume the F&E cistern is above the level of the top rads.
If you bleed them and air comes out until they are full, then they refill with air a day or so later, you have a problem with air being sucked into the system, the configuration of the pump/cold feed/open vent need to be corrected.

OR:
If they won't bleed or fill, the cold feed from the F&E is blocked and will need to be cleared (messy job).

Carefree, January 2011