andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

boiler bangs when zones shut down?

i have a new gwa hot water boiler model 175ns with 4 honeywell zone valves v8043e1012 controled with a argo az4cp when any zone shuts off i get a bang in the area of the valves it happens even right after i bleed each zone
macko, February 2011
It sounds like the new pump is too powerful, forcing the valves shut/open.
Look to fit a small system by-pass on the primary flow/return pipework.

Carefree, February 2011