andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

bosch zwb7-32 rd532 condensing boiler?

the pressure guage on the boiler keeps going to 3 & water keeps dripping out of the relief valve.I have drained the system to take it down to 1 bar, but when the heating comes back on it goes back up to 3 bar. Does anyone out there know how to fix this problem. Thanks Kev
Kev, March 2011
Further thoughts. Is expansion vessel seal blown so no space behind diaphragm for expansion, or simplest possibility, is the fill permanently connected to mains, and the shut off valve is letting by. My daughter has this boiler, and with fill pipe disconnected from the valve, the valve lets by so needs a cap.

Gonky, March 2011
Could be the expansion vessel needs to be larger

Gonky, March 2011
link Click here to see other fixes for Bosch ZWB7-32 RD532.