GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

switchmaster cylinder stat to honeywell cylinder stat?

on the switchmaster sct1 there are 4 wires-red-brown-blue-green/yellow,which do i use with a honeywell L641A 1039 4A 230V replacement? Regards.
davemac43, April 2011
Hi, Yes the green/yellow goes to earth

Dave McAllister, January 2015
Thanks for your reply,the red wire goes to earth,green/yellow goes to the same number as the programmer on the junction box,brown &blue go to the same numbers on the junction box as the midi valve.

Davemac43, April 2011
Confirm that the green/yellow is wired to earth, this would be the one not used in the Honeywell L641, it has no earth fixing point.
Don't just assume, make sure, as you are already aware, you're dealing with 220-240v ac and assumptions can be dangerous/fatal.

Carefree, April 2011