Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Jerry asked ... Alpine 7287?    |    Guy asked ... Gaggenau fridge alarm problem?    |    Click here to ask your question

worcester bosch 280 heating rads while running hot water?

While running the hot water Ie.Shower, all the radiators are getting hot. Now I know that during DHW demand the heating is 'switched' off, then when DHw demand stops waste heat is shunted to the rads, but never both at the same time.
This has always been the case until tonight when this has append. Also the pressure rose to 2.5 bars, which I don't think it normally does.

Does anyone have any ideas what may be causing this?

(worcester bosch 280 F)
Pete, June 2011
Fitted new diverter valve and all's well. :D

Pete, June 2011
Do you mean the diverter valve?

Pete, June 2011
three way valve sticking

colin smioth, June 2011