Suzanne asked ... Washing programme stops after 3 minutes?    |    Rif asked ... Kenwood Dishwasher KID60S20 leaking from front?    |    Fraser asked ... Spares for power craft ppcs 38cc?    |    FB asked ... Toyota Yaris Speed Camera Warning Beep?    |    Ela asked ... Worcester 30 Cadillac combi boiler won’t fire up and the EA?    |    Click here to ask your question

Can't get one 1/2 of radiator to heat. ?

Took rad off to decorate. Put back on. Back panel heats up ok after bleeding but front does not heat at all. Have bled front and back panels. Air came out of back and it is heating ok. Nothing came out of front. Not even water. What is going on?
needawin, January 2012
turn off radiator valves at both ends, screw vent out of rad , push a fine wire or needle into vent hole, it may be blocked , screw vent back into rad before opening valves, vent rad.

tvm, January 2012
when you took out did you flush out,if not flush out should be ok,what type of boiler combi you should fill with filling loop to 1.5 bar ,shut down rads which are getting hot water will run and air will purge out from header tank