I'm also having same trouble with the same boiler.f03.According to the installation manual f03 is when the 100'c safety thermostat trips in.
Possible cause-flow sensor not active or correctly located or no system circulation.
cure-check the correct positioning and operation of the flow sensor.
check the pump.
i suspect the pump has failed,maybe due to being inoperative during summer months.possible seizure.will post again when i find the cause and let you know.ps.is yours making loud banging noises when hot water is demanded and not circulating central heating?
eric walker, October 2006