Factory setting for the pump mode selector is 1. This will give pump operation on demand of the external controls. If you have no external controls (i.e. a link between 3 - 4 on the main terminal strip) the pump will run continuous. Position II is pump operation controlled by the boiler thermostat with a pump overrun of 20 seconds, position III is pump operation controlled by the heating switch on the facia. Finally position S is the same as II but with a pump overrun of 5 minutes. Position s is only on "hybrid" boilers. hope that helps!
andy, heating engineer. homer1981uk@hotmail.com, December 2006