Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

baxi 105he?

pressure rises above 3 bar when heating on. what could cause this
pete, February 2012
the expansion tank has lost its air bubble. it will either need refilling with air or may have burst internally and need to be replaced. Water gets bigger as it heats up (by about 4%) the expansion tank takes up that expansion and keeps the pressure steady.

I think the tank is on the back of a 105he accessed from the top via a metal panel. its the same type of valve as on a car tyre. Take the cap off the valve press needle in untill any air left in is gone. If water pours out it needs a new tank. If not pump up to 1bar ish while letting water out of the system. when water stops coming out the drain keep pumping it up till the gauge on the pump says 1 bar. then fill by the filling loop to 1 bar ish

geoff shuttle, February 2012
pressure does rise when working hard and red hot.What is the bar pressure when cold?

A1, February 2012