Karen asked ... Royal 480nt cash register?    |    andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    Click here to ask your question

baxi combi 80 Eco?

A plumber turned the pressure relief valve several times in the anti-clock wise dir ,now the system keeps blowing off to .5 bar no matter how many times i rechange the system to 2.5 bar i have tried turning the valve in the clock wise dir to no avail
kevin, February 2012
for 1 thing,you should not be charging to 2.5 bar, 1 bar is normal. system pressure will increase, as it gets hot, the relief valve operates at 3 bar. as you have it at 2.5 a lot of pressure is going out, when it operates, thats is probably why it drops to 0.5.
Turning the valve should not do anything except release pressure, But it is not the correct way, they can leak afterwards. Why did he turn it anyway, was it leaking? as turning it a few times can flush the valve seat and stop it from leaking.

SD, February 2012