Andrew - C asked ... Stannah 400?    |    Liam asked ... Belts for old WEBB Mower?    |    Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    Click here to ask your question

my prima 100f wont stop?

i have a problem in the cooler weather in that my boiler runs even when the controller is not calling for the boiler to come on ,to stop the boiler i have to turn it to 0 position ,i have changed the controller but it made no difference . anyone know where the problem lies?.
martin davie, October 2006
is it a 'y' plan system with one mid position valve or an 's' plan with two zone valves? you should be able to find them next to the hot water cylinder. If its an 's' plan you may find one of the valves is stuck open or the motorised head is faulty.

Paul, October 2006