Michael asked ... Mountfield empress drive belt?    |    John Barton asked ... How do i clear the TAM?    |    John asked ... How can I mend my binatone veva 1210 handset?    |    Kurt asked ... How can i mend my Aiwa HV-FX7700K?    |    Laetitia asked ... Toyota overlocker model 3400 D?    |    Click here to ask your question

My Vokera boiler builds pressure?

When I switch on my Vokera 24 boiler it quickley builds pressure up the needle goese right to the top then pores water out of the pipe out side then I have to refill it again.
Charlie s., October 2006
My vokera excell heating the dhw when the tap is turned on for a short period then the water runs cold, any idears

mm, October 2006
you should only refill it to 1.5 bar when cold , if thats what your doing the problem is the expansion vessel has lost its charge or has a burst diapragm , try recharging it ull have to let the pressure out of the system then check the charge in the vessel , footpump will fit, and if it needs to be recharged it says on the data badge of the vessel what the charge should be pump it up , if you get water out of the air point your vessel is burst and you need a new 1

andy plumb, October 2006