h3 code ideal izar he24 what is it?

I have ideal izar he 24 boiler fault on panel
showing h3 flashing up what is this
roy, March 2012
H.....3..... (DHW THERMISTOR ERROR)

Is there continuity between the
PCB and the thermistor ?
Remove the boiler DHW thermistor from the plate
heat exchanger and disconnect thermistor wires.
Are the thermistor values correct ?
Check resistance using a suitable multimeter
connected across the thermistor’s terminal pins
At 25 oC expect 9,700 - 10,300 Ohms
At 60 oC expect 2,400 - 2,600 Ohms
At 85 oC expect 1,000 - 1,100 Ohms
No = Replace the thermistor
YES
Is there continuity between the
PCB and the thermistor ?
Yes
Replace PCB
No
Check and replace wiring as necessary.