4 hours ago Ela asked ... Worcester 30 Cadillac combi boiler won’t fire up and the EA?    |    Alan asked ... Problem with JCB 3CX transmission?    |    Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    Click here to ask your question

How can i fix my Baxi Eco 80?

I have a Baxi Eco 80 boiler,sometimes not always whilst running hot water my radiators heat up whilst the heating is turned off.
Brian, June 2012
3 way valve{divertor]
DHW differential valve
plate heat exchanger
any 1,2 or all 3 components could be blocked or seized
only way tell for sure is to open it up & have a look

AWOL, June 2012