GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

Saunier Duval Combi Boiler Pressure Rises?

Hi

Hopefully someone can answer this problem for me please?

I have a Saunier Duval Thema Condens F30e Boiler which recently had the heat exchanger replaced (intermittent hot water). However, since it was replaced the pressure keeps rising in the system. The water and CH work fine but within about two hours the pressure will rise from 1.5 bar to around 2.9. This cuts out the CH but the tap water will still heat on demand as required.

If the mains water is isolated the pressure in the system remains steady. When the isolator is opened the pressure slowly increases (as described above), whether taps are used or not. The pressure always increases i.e. it doesn't fluctuate up and down, just slowly increases.

The items changed so far:
2 x thermistor sensors and a thermostat overheat (trying to solve the original problem)
Heat Exchanger (was the original problem)
3 way valve
Main Pump

Can anyone sugggest what the problem may be please?

Thank you
Brad, June 2012
It was the domestic hot water plate heat exchanger that was changed. As the increasing pressure only occurred after the original was replaced this does seem possible. Is this a common problem? Or could something not have been set up correctly when replaced?

Brad, June 2012
when you say heat exchanger replaced do you mean
the main heat exchanger? HEX
or the domestic hot water plate heat exchanger? PHX
pressure rise caused by pinholed PHX

AWOL, June 2012
link Click here to see other fixes for Saunier Duval.