Eed asked ... Brother KR850?    |    Lynne asked ... Disable Alarm Scantronic 9800?    |    Ron Minadeo asked ... Table won't close all the way?    |    Cam asked ... How can I fix my Bison 50 stairlift?    |    Alfred Briffa asked ... How to build a battery conversion adapter?    |    Click here to ask your question

how do i re prime boiler after oil running out?

oil ran out , so re placed oil ,now its triping out after start up 10 to 30 secs
roger, November 2006
Find the flexible hose that connects onto the burner on you boiler slacken it off until oil comes out (providing your tank is higher than the boiler),re connect and try again.Carefull though if your burner is a riello pressing reset without oil in the oil pump too many times can damage the pump (cost about £75.00).
Hope this helps.
Pete 100%Heating

Pete Brown, November 2006