Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

Vaillant VCWGB242E/282E?

I have high presssure showing after heating as gone off not returning to normal settings showing 2 to 3 bar need to drain off each day
Brian Ingoe, November 2006
Sounds like your filling loop is slightly open.Remove the braided hose to check this.

Pete 100% Heating ,Bristol 01454854067, November 2006