Fraser asked ... Spares for power craft ppcs 38cc?    |    FB asked ... Toyota Yaris Speed Camera Warning Beep?    |    Ela asked ... Worcester 30 Cadillac combi boiler won’t fire up and the EA?    |    Alan asked ... Problem with JCB 3CX transmission?    |    Lou asked ... Mac Allister 35cm electric lawn mower?    |    Click here to ask your question

Pressure reading over 3 bar?

Hi I have a Worcester 28CDI and recently noticed that the pressure is reading over the 3 bar level previously it was between 1 and 2, can anyone advise how you can reduce pressure every where I look its the opposite ,ie needing more to increase the pressure ,but cant find anything on reducing?
Gill, February 2013
If it is constantly reading over 3 bar then it may either the filling loop has been left open or the plate heat exchanger has pinholed and is cross leaking water from the dhw into ch, to reduce pressure bleed a rad until the pressure is between 1 & 2 bar on gauge, if pressure only rises to 3 bar whilst boiler running the it may be the expansion vessel at fault. If after all that the fault persists then you may need to call a professional or boiler manufacturer for a repair.

Steve, March 2013
u can bleed a rad from the air point it will gradually reduce the pressure as u take the water out

kash, February 2013