Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

Danfoss REP230 Thermostat Wiring?

Long story short, I have the above thermostat and had an installer try to replace it with the new NEST thermostat. It was faulty and I couldn't be bothered with the hassle of getting another one so I asked the installer to re-install my Danfoss.

It doesn't control the boiler at all (boiler doesn't go off when temperature is down low) and I've had an engineer out today. He told me he fixed it but alas it is still not working.

I noticed there is nothing connected to the "OFF" terminal. I am a complete lay-man with this but do you think this is the problem?
Brian1982, May 2014
There are several variations of stats if yours has got LIVE,NEUTRAL 3,4,5 and earth
1 = live
2 = neutral
3 = common
4 = load or on
5 = for for cooling or off
If there are only 4 connections just connect 1,2,3
Live Neutral and load

toptrish, May 2014