Tanzania asked ... How can i mend my sanyo fwbp505f q?    |    Mark Goodwin asked ... Mount field 725m ride on mower?    |    Joan Sorrentino asked ... Barcalounger issue?    |    David asked ... Not starting until I bang door closed?    |    Sharma asked ... Replacing pin for belt guard Ranch King Pro 14AT818H205?    |    Click here to ask your question

baxi wm532 rschb wont fire up?

boiler will only fire up when temp sensor is removed from boiler port, pilot light is ok,how many pumps should this type of boiler have? cheers
terry, December 2006
Most appliances only need the one pump, however some systems are designed to have two... I would suggest that you would only need the one with this appliance.


My question has to be, have you changed the thermostat yet?

GasAid.co.uk, December 2006