Jo asked ... How to engage clutch on old sewing machine to engage needle?    |    Jacky asked ... Miele Vacuum cleaner?    |    Ben asked ... Toyota Yaris French or Japanese?    |    Andy asked ... How can I mend my MacAlistair 450w hedge trimmer?    |    Felix asked ... Hitachi vt-m70em?    |    Click here to ask your question

Baxi 105 e ?

Can anyone tell me why the needle on pressure gauge risers when the central heating is put on ? I can only put heating on low to keep it at 2 on pressure gauge. Would be grateful if anyone has any ideas before calling an engineer ,
Sarah, February 2016
If the pressure is between 1 & 1.25 when the system is cold and the rises rapidly ( within 20 mins ) to 3 bar then there is a problem with the expansion vessel. If this is the case then you should get a registered engineer to address the problem

Mac, February 2016
When this happened to my Worcester condensor boiler i was advised to let more water into the system,this worked for me

James, February 2016
Water in the sealed system gets hot, expands, increasing the pressure in the system.

Check you have the correct pressure with the system cold.

RTFM, February 2016