Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

Expansion vessel full of hot water?

I have a Heatslave 20/25 and it stopped pumping water around the system. I thought it was the pump, but the expansion vessel is full of very hot water and may be the problem.
Can you advise me?
PhilB, April 2016
The full expansion vessel can't be the cause, but it IS a symptom of another problem.
There is something blocking the water flow after the expansion vessel, the water level within will obviously go up as it have nowhere else to go.

Turn the furnace OFF. Turn the pump off if it don't turn itself off. As the water cool down and contract, the water level will go back down.
Call a plumber to check the pipes now.

Electro, April 2016
\try this

https://www.youtube.com/watch?v=4meZgMAUecw&app=desktop

Roger, April 2016