Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

What sort of bypass do I need for a Potterton Netaheat 16/22?

I have a 15mm bypass (with valve) and a 22mm loop to a towel rail fitted to the Potterton Netaheat 16/22. I'm looking to replace the towel rail with one with 15mm fittings. Could this be a problem? Does the boiler need both loops or will one or other be sufficient to prevent overheating?
John More, January 2007
It will be fine... Are you 'S'-Plan or 'Y'-Plan as with the 'Y' you don't necessarily need it; with the 'S' a 15mm auto by-pass will be sufficient.

GasAid.co.uk, January 2007