Andrew - C asked ... Stannah 400?    |    Liam asked ... Belts for old WEBB Mower?    |    Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    Click here to ask your question

ikon-t boiler pressure too high?

When i turn my heating on and turn the temp up, the pressure goes from 1.5bar all the way up to 3bar causing the water to be ejected via the pressure release valve. Any ideas why the pressure within the boiler is so high to have to trip the pressure release valve?
mark gibbs, January 2007
expansion vessel my need replacing check this by having one of the rads half full of water if pressure doesn't go up then it does need replacing

gillard plumbing & heating, April 2008
Looks like the valve core is leaky, will buy a tool and tighten it or replace. Thanks for your help - much appreaciated. Mark.

mark gibbs, January 2007
expanssion vessel needs charging or split

hi-spec plumbing, January 2007