Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Susan asked ... How can I stop my steam iron spraying water with the steam?    |    Click here to ask your question

I have a alpha 240e combi boiler about eight years old?

I have noticed recently that radiator is getting hot when running hot water with boiler set on water only.also the water temp is not constant. When set to heating and water there is a big gurgle in bathroom radiator as soon as shower is turned off. I guess it could be the diverter valve but any ideas if it could be caused by anything else ?
Nigel, March 2007
i would agree with you too, had same problem on sime boiler. diaphragm in diverter valve perished, cost about £1 to fix

dave, March 2007