27 mins ago Ariana Orellana asked ... Code?    |    Lynnie asked ... BT Studio 4500 cordless telephone?    |    David Dawes asked ... How to recoil the starter spring - Champion R484TR?    |    peter high asked ... How can I set time on my Neff oven?    |    Michael asked ... Mountfield empress drive belt?    |    Click here to ask your question

how do I fix my riello 40 boiler after running out of oil?

I ran out of oil, i have oil now but the boiler fires up and then dies
Tracey Smyth, March 2007
you need to purge the oil throught to the oil pump as it sound like u have air in the line after running out u can do this by finding the screw on the oil pump marked v or p loosen the allen screw slightly and allow the air to be purged from the oil line do not remove screw as when oil comes out you might not be able to replace it hope this helps

steve, March 2007
link Click here to see other fixes for Riello.