Andrew asked ... Jcb cordless 20v combi drill?    |    marc asked ... La machine 1 type 813?    |    Andrew - C asked ... Stannah 400?    |    Liam asked ... Belts for old WEBB Mower?    |    Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Click here to ask your question

HOW CAN I STOP WATER COMING OUT OF THE 15mm PIPE THAT GOES OUT SIDE FROM MY?

I HAVE A POTTERTON COMBI GAS BOILER THE 15mm PIPE THAT GOES OUTSIDE KEEPS LEAKING WATER AFTER CENTRAL HEATING SWITCH ON .THE PRESSURE DROPS WHEN C/H SWITCH ON AFTER AWHILE I HAVE TO REPRESSURE TO GET H/W THIS IS O/K BUT AS SOON AS C/H SWITCH ON WATER APPEARS TO LEAK OUT OF PIPE OUTSIDE IT ONLY HAPPENS WHEN C/H ON.
MR J SPENCE, September 2007
u need to recharge the expansion vessle to 1 bar with the no back pressure on the boiler

kris, September 2007