GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

my baxi pressure bar goes upto 3 when i switch on the radiatoes?

normally my pressure bar is under the 1 and when i swithch the radiators on it works its way upto 3 into the red. otherwise it gives me hot water when i whant and the radiators work ok. how can i fix only the pressure bar.
my baxi is the model combi instant 105e
fil, November 2007
I have the same problem. How do you re-pressurise the expansion vessel?

Les, November 2007
it may be the expansion vessel

barry, November 2007
The expansion vessel most probably needs repressuring. This is the usual cause of over pressuring.

Mr A, November 2007
link Click here to see other fixes for Baxi 105E.